Small leak on CGH2 trailer (221)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Small leak on CGH2 trailer

A leak developed on a CGH2 tube trailer on the pigtail of one of the tube. The pigtail was cracked, possibly due to vibration. This trailer was tested the day before this incident and was found to be leak free. The trailer consisted of 10 tube, and each tube has a pigitail. Trailers are tested for leaks every fill.

Event Date
May 8, 1990
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

The INITIATING CAUSE was probably mechanical vibration from the road. The ROOT CAUSE could be (i) a shortcoming in the design, failing to take into account vibrations effect, or (ii) some mistake in the installation of the pigtail valve connection.

Facility Information
Application
CGH2 tube trailer
Specific Application Supply Chain Stage
Components Involved

Hose

Storage/Process Medium
Location Type
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Environmental Damage
0
Currency
Property Loss (onsite)

115

Property Loss (offsite)

0

Event Nature
Emergency Action

The emergency actions are not reported. From similar cases, it could be assumed that the pigtail connection was isolated and replaced. However, this would only have been possible for very low leak flow.

Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
References
References

Incident I-1990060084 of the US Pipeline and Hazardous Materials Safety Administration PHMSA: https://portal. phmsa. dot. gov/analytics/saw. dll?Portalpages&PortalPath=%2Fshared%2FPublic%20Website%20Pages%2F_portal%2FHazmat%20Incident%20Report%20Search (accessed September 2024)