Small leak on CGH2 trailer
A leak developed on a CGH2 tube trailer on the pigtail of one of the tube. The pigtail was cracked, possibly due to vibration. This trailer was tested the day before this incident and was found to be leak free. The trailer consisted of 10 tube, and each tube has a pigitail. Trailers are tested for leaks every fill.
Event Date
May 8, 1990
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences

The INITIATING CAUSE was probably mechanical vibration from the road. The ROOT CAUSE could be (i) a shortcoming in the design, failing to take into account vibrations effect, or (ii) some mistake in the installation of the pigtail valve connection.