Skip to main content

Small leak at a hydrogen transfer hose (1137)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Small leak at a hydrogen transfer hose

A leak occurred when transferring hydrogen from a trailer to the customer storage. The driver had just completed the pre-fill procedures and was starting to apply pressure to the fill hose, when he heard a leak coming from it. The driver immediately isolated the hose by shutting off the trailer manifold valve. The hose leaked for approximately 1 to 2 seconds. The driver terminated the fill process by using another hose and returned to his home facility. The leaking transfer hose was inspected and a small leak was detected at the crimped fitting. The hose was purchased new in 2004, last tested in 8/2007 and was due again for test 8/2008.

Event Date
June 13, 2008
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

The INITIATING CAUSE was the leak of the flexible hose. The ROOT CAUSE is unknown, the hose was regularly tested, unexpected ageing is the most plausible explanation.

Facility Information
Application
CGH2 tube trailer
Specific Application Supply Chain Stage
Components Involved

Hose

Storage/Process Medium
Storage/Process Quantity
267
Location Type
Operational Condition
Pre-event Summary

The driver had just completed the pre-fill procedures and was starting to apply pressure to the fill hose

Consequences
Number of Injured Persons
0
Number of Fatalities
0
Environmental Damage
0
Currency
Property Loss (onsite)

0

Property Loss (offsite)

0

Lessons Learned

Considering the small leak and very limited amount of hydrogen released, this incident is almost a near miss. According to the report, the failed component, a hose, had been regular inspected and tested, and the operator (the trailer driver) acted promptly and according to the procedure. A good example of how consequence of a leak can be controlled.

Event Nature
Emergency Action

The driver immediately isolated the hose by shutting off the trailer manifold valve.

Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
References
References

Incident I-2008070440 of the US Pipeline and Hazardous Materials Safety Administration PHMSA: https://portal. phmsa. dot. gov/analytics/saw. dll?Portalpages&PortalPath=%2Fshared%2FPublic%20Website%20Pages%2F_portal%2FHazmat%20Incident%20Report%20Search (accessed September 2024)