Small leak at a hydrogen transfer hose
A leak occurred when transferring hydrogen from a trailer to the customer storage. The driver had just completed the pre-fill procedures and was starting to apply pressure to the fill hose, when he heard a leak coming from it. The driver immediately isolated the hose by shutting off the trailer manifold valve. The hose leaked for approximately 1 to 2 seconds. The driver terminated the fill process by using another hose and returned to his home facility. The leaking transfer hose was inspected and a small leak was detected at the crimped fitting. The hose was purchased new in 2004, last tested in 8/2007 and was due again for test 8/2008.

The INITIATING CAUSE was the leak of the flexible hose. The ROOT CAUSE is unknown, the hose was regularly tested, unexpected ageing is the most plausible explanation.