Release of LH2 during transfer

During preparations for off-loading of a commercial tanker, the trailer experienced an overpressure causing the 50 psig (ca. 3. 5 bar) relief valve to open and also the rupture of the 70 psig (ca. 4. 8 bar) burst disc. Hydrogen was vented through the vent valve and the disc. A vapour cloud of about 25 feet in diameter resulted. Examination later also showed cracks in the carbon steel vent line. [Ordin, NASA (1974)]

Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

The liquid phase valve into the trailer transfer build-up coil was opened prior to opening the gas pressurization valve. Opening the pressurization valve resulted then in unrestricted large flows into the tank causing excessive pressures which opened the relief valve and ruptured the burst disc. Vibrations during transit may have caused the liquid phase valve to open. The trailer was almost completely full of liquid hydrogen which contributed to the accident. The flow of cold fluid caused the cracks in the carbon steel vent line.

Facility Information
Application
LH2 tanker
Specific Application Supply Chain Stage
Components Involved

PRV; burst disc

Actual Pressure
0
Design Pressure
0
Location Type
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Event Nature
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
References
References

Mishap no 16 in P. L. Ordin, Review of hydrogen accidents and incidents in NASA operations, 1974, NASA TM X-71565 https://ntrs. nasa. gov/citations/19740020344