Release from LH2 tanker during loading
A road tanker was being loaded with liquid hydrogen from a 15,000 gallon storage tank, when fire broke out after 1 inch rupture disc failed, ignition source was a loose connection in down stream piping. The ignition was not immediate after rupture.
Event Date
December 23, 1977
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING CAUSE was the opening of a burst disc. IGNITION SOURE was a loose connection in the vent pipe (the report is unclear, probably a spark was attributed to this loose cconnection). The report does not specify if the disc failed at the set nominal pressure (1) or prematurely (2). Depending on this, two different ROOT CAUSE can be suggested: Case 1: the tank was overfilled, with a ROOT CAUSE = wrong operation. Case 2: material/componet failure