Release of LH2 during transfer
While pressurizing a liquid hydrogen tanker for the transfer, a rupture disc burst. The tanker pressure was 22 psig (ca. 1. 5 bar). The relief valve was set at 27 to 29 psig (1. 9 to 2 bar). The tanker was moved to remote location and the disc replaced under loaded conditions. The transfer was resumed. However, during the operation, there was a leak through the vent valve. [Ordin, NASA (1974)]
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences

INITIATING CAUSE was due to the relief valve which did not operate. Because of this, the pressure may have increased sufficiently to cause the burst disc to fail. Leakage through the vent valve was attributed to water entering the system during repair to replace the burst disc.