Release of LH2 during transfer (366)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Release of LH2 during transfer

While pressurizing a liquid hydrogen tanker for the transfer, a rupture disc burst. The tanker pressure was 22 psig (ca. 1. 5 bar). The relief valve was set at 27 to 29 psig (1. 9 to 2 bar). The tanker was moved to remote location and the disc replaced under loaded conditions. The transfer was resumed. However, during the operation, there was a leak through the vent valve. [Ordin, NASA (1974)]

Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

INITIATING CAUSE was due to the relief valve which did not operate. Because of this, the pressure may have increased sufficiently to cause the burst disc to fail. Leakage through the vent valve was attributed to water entering the system during repair to replace the burst disc.

Facility Information
Application
LH2 tanker
Specific Application Supply Chain Stage
Components Involved

burst disc

Actual Pressure
0
Design Pressure
0
Location Type
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Event Nature
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
References
References

Mishap no 14 in P. L. Ordin, Review of hydrogen accidents and incidents in NASA operations, 1974, NASA TM X-71565 https://ntrs. nasa. gov/citations/19740020344