Release of LH2 during transfer
During an LH2 transfer from a tanker, the burst disc ruptured at 50 psi (ca. 3. 5 bar). The operator had turned on the pressure valve and left it unattended, permitting pressure build-up past the allowed 30 psi. Pressure limit for the operation was 30 psi (ca. 2 bar). [Ordin, NASA (1974)]
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes

The INITIATING CAUSE was the excess of maximal allowed pressure and consequent correct rupture of the burst disc. The ROOT CAUSE was the not following of the prescribed procedure. The operator left pressure valve unattended, permitting pressure build-up past the allowed 30 psi.