unplanned release of LH2 from tank
During loading of a LH2 storage tank, the vent valve on the tank was opened and then ignition occurred near the instant that the valve was fully open. A light pressure wave was produced. The cloud contained about 57 kg of hydrogen at ignition. Water was used to cool the area after which inspection showed a leak inside the vent valve body was still burning. The tank pressure was below 4 psig. [Ordin, NASA (1974)]
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences

The INITIATING CAUSE appears to consist in two separate sub-events: the opening of the vent valve with consequent formation of air-hydrogen explosive mixture at vent opening, and the crack in the body of the vent valve, which produced a local fire. A temporary venting system was being used with an unsatisfactory vent valve. Static discharge was assumed to be the IGNITION SOURCE. The report does not explain why the vent valve was opened, nevertheless the ROOT CAUSE could be tentatively identified in a combination of erroneous installation and operation of the temporary venting system and a material failure.