HIAD Nature Event - Release Type: Gas


This incident occurred in the turbine compressor system. A severe hydrogen ingress into the stator coolant system resulted in a fire in the stator coolant head tank (ignition source unknown). No…

A leak of a compression fitting lead to the build up of an explosive air/hydrogen mixture in the generator pit. The ignition of the mixture was caused by corona discharge. The resultant explosion…

The compressor-turbine unit tripped while on on-load, due to a serious fire between alternator and one of the bearing. The failure of a generator slip ring and of the hydrogen seal caused the leak of…
The explosion occurred in the condenser area of a steam turbine, two hours after the unit tripped due to a stator earth fault. The stator earth fault had damaged two hydrogen cooler tubes, which…
Ejection of rotor wedge material lead to vibration induced failure of components, including hydrogen seals. Serious fire resulted from hydrogen leakage, which subsequently lead to an oil fire.…
Explosion of hydrogen at slip ring end of an alternator. It was caused by a hose fracture within the generator casing, which led to a discharge of water into the casing and subsequent electrical…
SYNOPTICs The loss of the hydrogen side sealing oil pump and other problems in the sealing oil system resulted in the coolant hydrogen leaking from the generator. The hydrogen leaked for several…
A nuclear Power Plant experienced a main generator hydrogen fire. Although a senior reactor operator (SRO) and auxiliary operators from another shift were available immediately, the need to provide…
This incident occurred during maintenance works after an outage at a turbine and generator unit of the plant. At the time of the incident, 15 maintenance technicians had already been working on the…
A catastrophic failure of the low pressure turbine followed by fire and flooding severely damaged the generator. The main turbine automatically tripped due to an erroneous mechanical over speed…
The incident started at the unit removing CO2 from the process gas stream of a hydrocracking facility. (Catalysed Removal of Carbon Dioxide = Catacarb). Localized corrosion caused a pipe to fail and…
A leakage and fire occurred during normal operation at a medium-pressure hydrocracker of a refinery. This unit perform a desulphurisation and a decomposition of heavy gas oil. High-temperature and…
A sudden fire started at the hydrogen compressor of a refinery's hydrocracking unit.

The event occurred at a plant for the production of ethylene, and affected the unit for the hydrogenation of pyrolysis gasoline. During a shutdown operation of the hydrogenation plant, the…

A fire occurred in a hydrogen and catalyst loading lines of heavy oil unit. The most likely cause was that a hydrogen purge pipeline failed allowing hydrogen to escape. This mixed with hot oil…
A hydrogen leak occurred from a low temperature valve on an acetic acid plant. The leak ignited and the resulting fire burned for about an hour. There was considerable media attention, particularly…
Hydrogen line at ammonia plant sprang a leak which ignited. Fire put out immediately causing no damage.
The incident occurred at the direct desulfurization unit of heavy oil. A 130×90 mm oval opening occurred in the bypass pipe of the hydrogen sulphide absorption tower for the circulating gas, at a…
The explosion occurred during preparatory work to start a compressor that supplies hydrogen gas to a heavy oil direct desulfurization unit. The inspection cover of the crank case came off, injuring…
At a nuclear power plant, a fire occurred in the station's hydrogen storage facility while the plant was operating at 100% power. The fire was reported to the control room by a non-licensed operator…