Fire at a generator of a power plant
A catastrophic failure of the low pressure turbine followed by fire and flooding severely damaged the generator. The main turbine automatically tripped due to an erroneous mechanical over speed signal caused by high vibrations. The reactor, which was operating at 93 percent power, received an automatic scram signal triggered by the turbine trip. The high vibration was caused by catastrophic failure of the turbine blades. Ejected blade parts ripped through the turbine casing and severed condenser tubes and other piping. Water from the fire suppression system and the damaged water lines accumulated in the basement of the turbine building and the adjacent radioactive waste processing building. There was also a hydrogen fire in the generator's exciter due to breakage of generator sealing. The reactor scrammed and the safety systems worked as expected.
Event Date
December 25, 1993
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
INITIATING CAUSE was high vibration and sudden failure of the turbine blades. ROOT CAUSE(S) Safety systems functioned properly. Some sources reported the lack of emergency procedure in case of water flooding. According the "List of nuclear power accidents by country" provided by Wikipedia, the main turbine experienced this major failure due to improper maintenance (ttps://en. wikipedia. org/wiki/List_of_nuclear_power_accidents_by_country (accessed November 2020).