Fire at a hydrogenation unit of a petrochemical plant
The event occurred at a plant for the production of ethylene, and affected the unit for the hydrogenation of pyrolysis gasoline. During a shutdown operation of the hydrogenation plant, the recycled gas leaked and ignited at the top flange of the hydrogenation reactor. The normal operation pressure of the reactor was about 2. 8 MPa and the temperature about 350 °C. During the transient triggered by the shutdown, the gas started leaking when it reached 150 °C and a pressure of 1. 3 MPa. The reason of the leak was an insufficient tightening torque applied at the start-up. Due to this insufficient torque, the flange started to leak due to the decrease of both falling temperature and pressure at shutdown.

The INITIATING/direct cause was the recycled hydrogen gas leak at a reactor flange. The loss of confinement was due to the fact that the flange bolt tightening torque applied at the start-up had been insufficient, and that the temperature reduction rate during shutdown was too quick, worsening the lack of tightness due differential dilatation of the joint materials. A contributing cause was that a quantitative control of tightening torque was not carried out, hinting at a human error or a shortcoming of the maintenance procedures.