Fire at the desulphurisation unit of a refinery (613)
This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.
Fire at the desulphurisation unit of a refinery
The explosion occurred during preparatory work to start a compressor that supplies hydrogen gas to a heavy oil direct desulfurization unit. The inspection cover of the crank case came off, injuring an operator. Normally, nitrogen was supplied to purge the case , displacing the hydrogen leaking from the shaft seal of the compressor cylinder. The accident investigation revealed that the nitrogen flow meter was broken, causing almost no gas to flow. It is assumed that the hydrogen leaking from the shaft seal of the cylinder entered the crankcase, ignited and burned due to static electricity. The expansion force of the explosion caused the inspection cover of the crankcase to fly off.
The INITIATING CAUSE was the failing of the nitrogen system supposed to purge the compressor crankcase free of hydrogen. The failure to purge was due to a broken flow metre which was indicating nitrogen flow while almost no nitrogen was flowing The ROOT CAUSE was a lack of proper inspection and maintenance.
We are professional and reliable provider since we offer customers the most powerful and beautiful themes. Besides, we always catch the latest technology and adapt to follow world’s new trends to deliver the best themes to the market.
Contact info
We are the leaders in the building industries and factories. We're word wide. We never give up on the challenges.
The INITIATING CAUSE was the failing of the nitrogen system supposed to purge the compressor crankcase free of hydrogen. The failure to purge was due to a broken flow metre which was indicating nitrogen flow while almost no nitrogen was flowing The ROOT CAUSE was a lack of proper inspection and maintenance.