Fire at the storage of a power plant
At a nuclear power plant, a fire occurred in the station's hydrogen storage facility while the plant was operating at 100% power. The fire was reported to the control room by a non-licensed operator who saw the fire start after he had aligned valves at the hydrogen storage facility in preparation for putting the hydrogen injection system into service. The operator escaped injury because he was wearing fire retardant protective clothing and was able to quickly scale a 7 foot high fence enclosing the hydrogen area.
Event Date
January 14, 1999
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The licensee identified the lack of effective maintenance as a root cause of the hydrogen fire event at JAF. INITIATING cause was the failure of three valves failed, starting the fire. According to the root cause evaluation, all of the failures were due to an inadequate preventive maintenance program by the hydrogen system vendor and inadequate system monitoring and management oversight by JAF.