- Home
-
Resources
- Center for Hydrogen Safety
- Hydrogen Fuel Cell Codes and Standards
- Paper & References
- Web-based Toolkits
- Workforce Development

- Contact
- About H2Tools
A hydrogen release occurred at hydrogen storage unit of a manufacturing plant in an urban area. The storage unit was a 9,000-gallon (34,069-liter) liquid hydrogen storage vessel. Its internal…
Compressed hydrogen escaped from reactor due to faulty gasket [Zalosh and Short, 1978]
During the pre-launch checkout, a check valve failed in the "open" position and an accidental venting of liquid hydrogen occurred. The event caused an unscheduled check and replacement…
Safety disc ruptured on LH2 tanker during offloading. The supply was refused due to possible contamination. [Ordin, NASA (1974)]
While disconnecting the liquid hydrogen filling line from the tanker, hydrogen escaped burning the man who was holding the hose; he was burned on hands and stomach. [Ordin, NASA (1974)]
During an LH2 transfer from a tanker, the burst disc ruptured at 50 psi (ca. 3. 5 bar). The operator had turned on the pressure valve and left it unattended, permitting pressure build-up past the…
While pressurizing a liquid hydrogen tanker for the transfer, a rupture disc burst. The tanker pressure was 22 psig (ca. 1. 5 bar). The relief valve was set at 27 to 29 psig (1. 9 to 2 bar). The…
During preparations for off-loading of a commercial tanker, the trailer experienced an overpressure causing the 50 psig (ca. 3. 5 bar) relief valve to open and also the rupture of the 70 psig (ca.…
A full liquid hydrogen tanker was parked off highway to permit drivers to eat and switch seats. While at site, high pressure caused safety devices to function. No fire or damage. [Ordin, NASA…