Release of hydrogen
A temperature probe on a hydrogen make up gas compressor blew out from its compression fitting. This resulted in a release of hydrogen. The incident occurred due to a fatigue failure of the compression fitting. Plant was shut down immediately, preventing any further release of hydrogen. Company are carrying out a full investigation into the housing failure. Vibration, manufacture and installation are all being considered as possible reasons for the failure. There were 20 such probes on the plant and these have all been removed until the cause of the failure could be established.
Event Date
September 16, 1999
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING/direct cause was a loss of confinement due to the failure of a temperature probe, possibly due to vibrations. Contributing causes were considered manufacturing and installation shortcomings.