Release of hydrogen (329)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Release of hydrogen

A temperature probe on a hydrogen make up gas compressor blew out from its compression fitting. This resulted in a release of hydrogen. The incident occurred due to a fatigue failure of the compression fitting. Plant was shut down immediately, preventing any further release of hydrogen. Company are carrying out a full investigation into the housing failure. Vibration, manufacture and installation are all being considered as possible reasons for the failure. There were 20 such probes on the plant and these have all been removed until the cause of the failure could be established.
Event Date
September 16, 1999
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING/direct cause was a loss of confinement due to the failure of a temperature probe, possibly due to vibrations. Contributing causes were considered manufacturing and installation shortcomings.
Facility Information
Application Type
Application
Unknown
Specific Application Supply Chain Stage
Components Involved
Hydrogen compressor, temperature probe
Storage/Process Medium
Location Type
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Investigation Comments

An investigation was performed to determine what may have caused the failure. Until conclusions are drawn 20 similar probes on site have been removed from service.

Event Nature
Emergency Action
Plant was shut down immediately, preventing any further release of hydrogen.
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Event description provided by HSE, original source confidential