Release of hydrogen from LH2 storage tank
A leak occurred at a of a liquid withdrawal valve of a liquid hydrogen storage tank. The hydrogen escaped at the flange between the valve body and the upper part of the valve (flange with tongue and groove). 40 kg of hydrogen were lost. The accidental release was due to the use of bolts different from those prescribed. By using the wrong ones (old bolts), the bolt material was able to flow at the specified tightening torque. This meant that there was insufficient tightening torque, which led to a leak.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The INITIATING CAUSE was the lack of tightness of a flange, due to the erroneous use of bolts on a flange. The ROOT CAUSE is related to a human error, to lack of knowledge and to the absence of clear procedures.