Release of toxic and flammable mixture from a hydrogenation reactor (95)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Release of toxic and flammable mixture from a hydrogenation reactor

The incident occurred in the hydrogenation reactor and products cooling unit. The reactor operated under vacuum conditions and the cooling medium was water. Toxic, flammable and explosive substances (flammable gases, hydrogen sulphide and hydrogen) escaped to the open air from a bend in the water cooler. The heat-exchanger of the cooling unit was corroded by the action of the hydrogen sulphide contained in the reaction products. The hydrogen sulphide emission caused bad odour in the surroundings of the plant area. The population was alerted.
Event Date
March 8, 1991
Record Quality Indicator
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING cause was the corrosion of the material by hydrogen sulphide.
Facility Information
Application Type
Application
hydrogenation reactor
Specific Application Supply Chain Stage
Components Involved
hydrogenation reactor, cooling unit
Storage/Process Medium
Storage/Process Quantity
100
Location Type
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Post-event Summary

Released amount of flammable gases = 145 kgReleased amount of hydrogen sulphide = 55 kg Released amount of hydrogen = 100 kg

Event Nature
Emergency Action
INTERNAL TO THE ESTABLISHMENT: The accesses to the installation were blocked and the reactor contents was sent to the flare system. Hydrogen sulphide concentration measurements were carried out. EXTERNAL TO THE ESTABLISHMENT: The hydrogen sulphide emission caused bad odour in the surroundings of the plant area. The population was alerted.
Release Type
Release Substance
H2 H2S hydrocarbons
Hydrogen Release Concentration (%)
0.00
Release Amount (kg)
100.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Description of the event in the European Database eMARS