Skip to main content

Release of hydrogen during hydrogenation (1090)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Release of hydrogen during hydrogenation

The event occurred at the hydrogenation unit of a pharmaceutical company. 145 kg of hydrogen were released the atmosphere at the gas circulation pump, due to a maintenance error . A specialist company (third-party company), had replaced the cylinder head of pump, but during assembly they did not re-installed the prescribed temperature sleeve for the thermometer (the temperature sleeve is the pressure-bearing element). The safety flare of the affected plant was triggered, the plant operations management and plant fire brigade were called on duty, the hydrogen supply to the neighbouring hydrogenation unit was stopped and the system was switched to circular operation.
Event Date
October 14, 2011
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING CAUSE was an error during re-assembling of the system after maintenance. A possible contributing CAUSE could be a lack of maintenance instructions, or their shortcoming.
Facility Information
Application Type
Application
Farmaceutical manufacturing
Specific Application Supply Chain Stage
Components Involved
hydrogen recirculation pump
Storage/Process Medium
Actual Pressure
20
Location Type
Operational Condition
Pre-event Summary
Maintenance works had been completed by a third party.
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Environmental Damage
0
Property Loss (onsite)
0
Property Loss (offsite)

0

Post-event Summary

Only operative costs due to loss of hydrogen and production stop.

Event Nature
Emergency Action
The safety flare was triggered, so that the leaked hydrogen could be released safely. Factory fire brigade and factory operations management were called on site. The hydrogen supply was stopped at the neighbouring hydrogenation plants and the system was operated in closed-loop mode.
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Event from German database ZEMA https://www. infosis. uba. de/index. php/en/binaries/asset/zema_ereignis/16311/pdf (accessed December 2023)