Release of hydrogen during hydrogenation
The event occurred at the hydrogenation unit of a pharmaceutical company. 145 kg of hydrogen were released the atmosphere at the gas circulation pump, due to a maintenance error . A specialist company (third-party company), had replaced the cylinder head of pump, but during assembly they did not re-installed the prescribed temperature sleeve for the thermometer (the temperature sleeve is the pressure-bearing element). The safety flare of the affected plant was triggered, the plant operations management and plant fire brigade were called on duty, the hydrogen supply to the neighbouring hydrogenation unit was stopped and the system was switched to circular operation.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING CAUSE was an error during re-assembling of the system after maintenance. A possible contributing CAUSE could be a lack of maintenance instructions, or their shortcoming.