Release of hydrogen from a LH2 storage tank
A hydrogen release occurred at hydrogen storage unit of a manufacturing plant in an urban area. The storage unit was a 9,000-gallon (34,069-liter) liquid hydrogen storage vessel. Its internal pressure increasing beyond the maximal allowed value and a safety relief device (a burst disk) activated releasing hydrogen into the atmosphere through the vent stack. The hydrogen jet rose approximately 15-20 feet (4. 6-6. 1 meters) in air, but it did not ignite. The industrial gas company responsible for the cryogenic installation was notified. They sent service technician who found the tank pressure at zero and the burst disk blown, switched the three-way diverter valve to the other safety relief device and replaced the burst disk which had activated. There were no injuries or damage from this incident, the hydrogen safety venting equipment functioned properly. The hydrogen was released without ignition, and since storage was in open space, no cumulation of gas in closed space occurred/ Normal operations could resume after it was determined that there were no unsafe conditions. However, approximately seven months later, the burst disk that had been replaced in the first incident ruptured for the same reasons. No outside emergency response was involved with this second hydrogen venting incident, as once again the pressure relief system worked as designed.

The INITIATING CAUSE was the correct activation of a burst disk due to overpressure. The cryogenic storage vessel had not been used for a (unspecified) long period, so that temperature gradient from ambient air temperature (60°F/16°C) through the vessel vacuum-jacketed walls were able to rise the internal temperature. The normal storage pressure for this vessel was 150 psi (10. 3 bar). A factor contributing to a premature activation was the existence of a backpressure against the disk. The ROOT CAUSES could be a combination of a lack of regular and effective inspection and of a inadequate venting design related to the existence of a backpressure of the burst disk. However, regarding this latter point, see diuscssion udner Lesson Learnt).