Skip to main content

HIAD Facility - Storage Medium: Gas


The explosion was caused by the ignition of hydrogen during reaction with sodium metal. The Chemistry Department routinely dried solvents using metallic sodium. This leaves an excess of sodium metal,…
A release of a mixture of hydrogen, nitrogen and ammonia ignited and exploded in the ammonia synthesis unit. The release was due to a cracked pipe and occurred at the level a flange situated at the…
The event took place in the on one out of the seven reactors for ammonia synthesis. The day of the accident, preparation works for the decennial pneumatic test (previous pneumatic test was carried…
A mechanical failure occurred in a gasification reactor, which caused a violent (abrupt, sudden) depressurisation of the reactor. The consequences were the projection of tiles of the refractory…
The event occurred at the hydrogen production unit of the ammonia production plant. An air-hydrogen mixture formed in the building hosting a water pump which fed water to a vessel that contained…
The event occurred during welding works which ignited accidentally released hydrogen. The plant had been partially shut down for repairing works to a pipe affected by internal cracks. The repairing…

[Note of HIAD event validator: The event description relates to a real accident, the details of which however are not publicly available. The descriptors are based on the analysis provided by the…

Explosion in an electrolyser producing chlorineThe explosion occurred after the opening of an auxiliary circuit-breaker. The opening of the auxiliary circuit breaker trigger the shut down of the…
The explosion occurred in a copper electroplating plant test furnace when starting the operation of copper plating. A tinned copper pipe had been placed inside another copper pipe and lined with…
An explosion occurred in an electrostatic precipitator whilst it was being accessed for maintenance. The explosion caused an inspection hatch cover, which had been unbolted, to be blown off and…
Works at the power grid of a hydrogen production unit is at the origin of the sequence of the following events: 1. Fusion of a safe fuse triggering the closure of a valve on the manifold of a pistons…
At an agrochemical plant, an explosion occurred near a drained hydrofluoric acid tank, when 4 employees were welding on adjacent pipelines. An investigation was launched to determine this accident’s…
An explosion occurred in the teat treatment workshop of this site. The explosion was centred in the electrical control panel of the High Velocity Oxy Fuel (HVOF) thermal spraying equipment. The…

An internal explosion occurred in a cone-roof gas oil tank. The explosion completely ruptured the weak roof-to-shell weld seam and projected the roof into the diked area beside the tank. The…

In a chlorine manufacturing unit, an explosion occurs in the room of the electrolysis cells. The accident occurs during the start-up phase of the unit, it is due to the presence of hydrogen in the…
During functional tests of the system, a major quantity of hydrogen-containing gas was released from an adsorber, followed by its ignition. After the alarm was released the feed of the adsorber was…

An explosion occurred in an industrial cleaner, blowing off and shattering the cover from the top of the machine. It is believed that the explosion was caused by accidental formation of hydrogen…

The Microbiological Anaerobic Chamber of approximately 2 m3 capacity was containing an explosive mixture of hydrogen and air. A fire followed the explosion, but was rapidly extinguished by staff…

During a test in which GH2 was driving gas, an explosion occurred in the test section. The drive chamber was over-pressurized to 3500 psi (240 bar). The test section failed; windows designed for a…

Fire in bulk hydrogen storage compound. Pressure gauge shut off valve spindle blown out (could be completely unscrewed and removed). The subsequent leak ignited by unknown source. No injuries…