Explosion in coating spray equipment
An explosion occurred in the teat treatment workshop of this site. The explosion was centred in the electrical control panel of the High Velocity Oxy Fuel (HVOF) thermal spraying equipment. The violent explosion propelled shrapnel, killing one person present. Four further personnel were injured. The hydrogen, leaked from a loose connection on the flashback arrestor of the unit, then migrated into the upper compartment of the HVOF console. At the point, an explosion when the hydrogen was ignited by a spark from any one of the electrical switches or relays contained there. The leaking connection was on a component which in all probability had only just been replaced. It is probable that the new arrestor, tightened the connections by hand and intended to tighten them with a spanner later but forgot to do so. Two recently drilled holes in the barrier partition of the HVOF console provided a potential leakage path for hydrogen into the electrical cabinet. Purge air which is intended to pressurise the electrical cabinet to prevent flammable gas ingress was not connected at the time of the explosion. The hydrogen pipework had not been leak tested prior to recommissioning. Safety systems to prevent flammable gas ingress into the electrical cabinet had been disconnected or bypassed.
Event Date
April 24, 1998
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITATING CAUSE was a loose hydrogen connection, probably due to the fact that it had not been tightened when replacing the connection. The ROOT CAUSES were a combination of lack of safety measures, shortcoming in the existing procedure and modification to the facility without executing a new risk assessment.