Explosion in an electrostatic precipitator (301)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Explosion in an electrostatic precipitator

An explosion occurred in an electrostatic precipitator whilst it was being accessed for maintenance. The explosion caused an inspection hatch cover, which had been unbolted, to be blown off and created a fireball which engulfed an electrician causing minor injuries. The sequencing of the shutdown tasks was fundamentally flawed as the spades were introduced immediately prior to the opening up of the vessel, after the 1. 5 day steam purge and 3. 5h cooling period. Leakage past the inlet gate valves would allow a flammable atmosphere to develop as the main constituents of coke oven gas are hydrogen, methane, carbon monoxide etc. The exact source of ignition cannot be established, the probable source was pyrophoric deposits in the vessel.
Event Date
November 10, 1998
Record Quality Indicator
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
INITIATING cause: probably leakage of the combustible gas mixture (hydrogen, methane, carbon monoxide) ignited by pyrophoric deposits. ROOT cause: mistakes in the maintenance procedure, specifically lack of gas detection step.
Facility Information
Application Type
Application
generic metal processing
Specific Application Supply Chain Stage
Components Involved
Electrostatic precipitator of a coking plant
Storage/Process Medium
Location Type
Operational Condition
Pre-event Summary
The facility was under maintenance.
Consequences
Number of Injured Persons
1
Number of Fatalities
0
Event Nature
Release Type
Release Substance
H2, CH4, CO
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Event description provided by HSE, original source confidential