Explosion in an electrostatic precipitator
An explosion occurred in an electrostatic precipitator whilst it was being accessed for maintenance. The explosion caused an inspection hatch cover, which had been unbolted, to be blown off and created a fireball which engulfed an electrician causing minor injuries. The sequencing of the shutdown tasks was fundamentally flawed as the spades were introduced immediately prior to the opening up of the vessel, after the 1. 5 day steam purge and 3. 5h cooling period. Leakage past the inlet gate valves would allow a flammable atmosphere to develop as the main constituents of coke oven gas are hydrogen, methane, carbon monoxide etc. The exact source of ignition cannot be established, the probable source was pyrophoric deposits in the vessel.
Event Date
November 10, 1998
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
INITIATING cause: probably leakage of the combustible gas mixture (hydrogen, methane, carbon monoxide) ignited by pyrophoric deposits. ROOT cause: mistakes in the maintenance procedure, specifically lack of gas detection step.