Explosion in an ammonia production plant
The event occurred during welding works which ignited accidentally released hydrogen. The plant had been partially shut down for repairing works to a pipe affected by internal cracks. The repairing schedule foresaw grinding and external welding of the defective parts. Despite the successful gas venting and system purging phase which guaranteed the drying of the pipe section, further water leakage was hindering the work, so that additional measures was taken, also to avoid too much gas waste. The hydrogen entered the system by a leaking valve, undetected at the time of job preparation and during subsequent checks. A welder was slightly injured. There was no damage to the plant.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The direct cause of the incident was the failure to adequately isolate hydrogen from the section of the system which was undergoing repairing works. Despite a succesful purging and the negative results of hydrogen detection, the detection procedure was not designed in such a way to reveal hazardoud concentration of hydrogen able to develop an explosive mixture with air during opening to air. The root cause was the inadequate management system, which failed to identify the hazard and to take the necessary preventive measures.