Explosion in an industrial gas plant
Works at the power grid of a hydrogen production unit is at the origin of the sequence of the following events: 1. Fusion of a safe fuse triggering the closure of a valve on the manifold of a pistons compressor, whose function was to raise the pressure from 50 mbar at the exit of the gasometer to 250 bar. 2. As a consequence of the closure of the valve, the dome of the gasometer filled with hydrogen up to the maximal level, after which the regulation valve of the storage system closed. 3. At this moment, a zone of under-pressure at the aspiration pipe of the compressor, causing the suction of air from outside, which formed with hydrogen an explosive mixture which auto-ignited. 4. The explosion caused the failure of the pressurised system: two pressure vessels, pipes and other parts of the plant were largely damaged, including the brick building hosting the unit. 5. Three plant keepers, which were in the near building, were seriously injured by an iron pieces breaking into the building.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
Human failure during repair works that led to the malfunctioning of the hydrogen-high pressure condenser.