The DC power system was serving as back-up power and was based on a battery storage system. It had been taken off-line to be replaced with a more modern system. After its replacement, at the…

A steam turbine/generator tripped due to an unknown hydraulic control oil system failure. The generator breaker opened, but the emergency valve (throttle valve) did not closed completely. Within 30…

Explosion as a result of detonation of gases inside container in turbine section causing 2 casualties .

Explosion in generator area, thought to be hydrogen leak as a result of radial lead seal failure. Extensive plant damage.
In an electricity production plant, hydrogen leaked from a tank supplying the colant to the generator. The leaked hydrogen iognited and formed a fireball. Possible involvement of sealing oil not…

The fire occurred at the turbine-generator unit of a power plant. A first hydrogen leakage took place from a 4 bolt flange. It ignited producing a small but intense flame, causing further hydrogen…

Hydrogen fire in the compressor-turbine chamber of a power plant. The hydrogen leaked from the generator terminal bushing into unventilated terminal segregated bulbar ducting (this is a duct used…

The incident occurred at the hydrogen coolant circuit, when purging the hydrogen with carbon dioxide and air, aiming at finding a leak. Following a preliminary investigation, the power plant company…
There was a massive explosion at one of the generator-turbine units of a coal-based power station. Undetected hydrogen leak from the generator was identified as a major trigger. According to the news…
The incident occurred at a power generator during the shutdown of one reactor unit. Hydrogen leaked from the cooling circuit of the generator due to damaged sealing. The hydrogen ignited. The fire…
A hydrogen leak sparked a fire at a power plant, burning a 30-foot hole in the roof. Only one of the plants four turbines were shut down.
A hydrogen leak occurred in in the cooling system of electricity generation part of the in a nuclear power plant. .
It was a small incident in a heat-electric power plant. The alarm was registered at 11:26 and the fire was extinguished at 12:03. The incident took place during tests using the reserve power…
A hydrogen leak occurred on the a coolant pipe of an electrical generator located in the turbine building, at 200 m from the reactor. Because of the welding works ongoing at that moment on the pipe,…
A malfunction in the turbine-generator unit resulted in a fire and forced the operators to manually shut down the nuclear reactor. The seals containing the hydrogen hydrogen used as a coolant were…

The explosion occurred at a hydrogen drier used for the treatment of the hydrogen used as coolant in a power generator. The hydrogen leaked, entered the contactor panel box of the drier and was…

This incident occurred in the turbine compressor system. A severe hydrogen ingress into the stator coolant system resulted in a fire in the stator coolant head tank (ignition source unknown). No…

A leak of a compression fitting lead to the build up of an explosive air/hydrogen mixture in the generator pit. The ignition of the mixture was caused by corona discharge. The resultant explosion…

The compressor-turbine unit tripped while on on-load, due to a serious fire between alternator and one of the bearing. The failure of a generator slip ring and of the hydrogen seal caused the leak of…
The explosion occurred in the condenser area of a steam turbine, two hours after the unit tripped due to a stator earth fault. The stator earth fault had damaged two hydrogen cooler tubes, which…