Fire - hydrogen (284)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire - hydrogen

Hydrogen fire in the compressor-turbine chamber of a power plant. The hydrogen leaked from the generator terminal bushing into unventilated terminal segregated bulbar ducting (this is a duct used for power cables). Ignition source not stated.

Event Date
November 12, 1986
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

INITIATING CAUSE Hydrogen leak from the power generator coolant system ROOT CAUSE The fact hat the leaked hydrogen could access the electrical cable duct seems to point at shortcoming in risk assessment, reflected in shortcomings in design. It could be, however, also be a wrong installation of the components.

Facility Information
Application Type
Application
unspecified type of power plant
Specific Application Supply Chain Stage
Components Involved

generator, cooling system, pipe

Storage/Process Medium
Location Type
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Event Nature
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
References
References

Event description provided by HSE, original source confidential