Fire - hydrogen
Hydrogen fire in the compressor-turbine chamber of a power plant. The hydrogen leaked from the generator terminal bushing into unventilated terminal segregated bulbar ducting (this is a duct used for power cables). Ignition source not stated.
Event Date
November 12, 1986
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences

INITIATING CAUSE Hydrogen leak from the power generator coolant system ROOT CAUSE The fact hat the leaked hydrogen could access the electrical cable duct seems to point at shortcoming in risk assessment, reflected in shortcomings in design. It could be, however, also be a wrong installation of the components.