Explosion at a turbine-generator of a power plant
The DC power system was serving as back-up power and was based on a battery storage system. It had been taken off-line to be replaced with a more modern system. After its replacement, at the moment of switching it on, it caused a zeroing of the voltage and the loss also of the AC powers, which was providing power station control. The control room lost any information on the operation of the station, which could not be disconnected from the grid or shut down safely. The turbine generator spun, and without power to the oil pumps and to the oil sealing the hydrogen coolant, the cooling power disappeared. Eventually turbine and generator failed mechanically igniting the escaping hydrogen. No-one was injured. An extensive blackout was the main consequence.

The INITIATING CAUSE was a loss of power controlling the power plant, due to the tripping of circuit breakers. This induced a loss of control on the operations, the running out of control of the turbine-generator unit and eventually the spilling of the oil and hydrogen used as coolants. The ROOT CAUSE was severe shortcoming in the design of the interconnection and interlocking of both the AC and DC systems and a lack of redundancy. Moreover, a failure to implement effective process safety practices at the plant was reported as result of the investigation.