Explosion in a power plant (164)
This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.
Explosion in a power plant
A steam turbine/generator tripped due to an unknown hydraulic control oil system failure. The generator breaker opened, but the emergency valve (throttle valve) did not closed completely. Within 30 seconds of the generator circuit breaker opening, the turbine accelerated from 3600 rpm to an estimated over-speed of 6000 rpm, resulting in the catastrophic failure of multiple components of the turbine. Seal and bearing lube oil were released under pressure, because the emergency battery-powered lube-oil pumps continued operating. The leaking lube-oil ignited, causing an intense fire around and below the damaged machine. The exciter and bearings were ripped from their mountings, causing total destruction of the generator. The generator shell was punctured, releasing hydrogen coolant which accumulated in the roof space of the turbine hall before exploding a few seconds later. The blast blew out ~ 30% of the turbine hall exterior block wall. Falling masonry damaged 3 outdoor transformers, rupturing associated oil coolers and initiating an oil fire. Fortunately, the incident occurred on a Saturday evening with few employees on site. On a weekday, 14 people would have been in imminent danger as they normally work in a nearby electrical workshop where a wall collapsed.
INITIATING CAUSE of turbo-generator set disintegration was turbine over-speed caused by a unclear malfunctioning of the control system. CONTRIBUTING CAUSES to the events escalation were: (i) The malfunctioning of the trip and throttle valve of the turbine: when the generator breaker opened, they kept feeding steam to the turbine, causing over-speed (ii) The continuous release of lube oil, feeding the oil fire (iii) The release of hydrogen and accumulation into a confined room, increasing the severity of the explosion. (iv) The damage to the hall structure due to the explosion, with consequent masonry falling on external transformers and initiating a transformer insulating oil fire. ROOT CAUSES included: 1) Inadequate preventative maintenance (the T&T valves had been affected in the past by several malfunctioning), 2) There were deviations from the operations prescribed, 3) The critical equipment of the systems had not been safe-tested.
We are professional and reliable provider since we offer customers the most powerful and beautiful themes. Besides, we always catch the latest technology and adapt to follow world’s new trends to deliver the best themes to the market.
Contact info
We are the leaders in the building industries and factories. We're word wide. We never give up on the challenges.
INITIATING CAUSE of turbo-generator set disintegration was turbine over-speed caused by a unclear malfunctioning of the control system. CONTRIBUTING CAUSES to the events escalation were: (i) The malfunctioning of the trip and throttle valve of the turbine: when the generator breaker opened, they kept feeding steam to the turbine, causing over-speed (ii) The continuous release of lube oil, feeding the oil fire (iii) The release of hydrogen and accumulation into a confined room, increasing the severity of the explosion. (iv) The damage to the hall structure due to the explosion, with consequent masonry falling on external transformers and initiating a transformer insulating oil fire. ROOT CAUSES included: 1) Inadequate preventative maintenance (the T&T valves had been affected in the past by several malfunctioning), 2) There were deviations from the operations prescribed, 3) The critical equipment of the systems had not been safe-tested.