HIAD Specific Application Supply Chain Stage: Hydrogen As Coolant


Ejection of rotor wedge material lead to vibration induced failure of components, including hydrogen seals. Serious fire resulted from hydrogen leakage, which subsequently lead to an oil fire.…
Explosion of hydrogen at slip ring end of an alternator. It was caused by a hose fracture within the generator casing, which led to a discharge of water into the casing and subsequent electrical…

The incident started with the cracking of the low-pressure turbine blades. This caused an unbalance to turbine generator rotor which led to the failure of the bearings and the loss of confinement…

During a turbine testing at 100 percent power, a problem developed in the auto-stop trip system, which led to a turbine and reactor trip. The turbine stop valves closed as expected, but after closure…
SYNOPTICs The loss of the hydrogen side sealing oil pump and other problems in the sealing oil system resulted in the coolant hydrogen leaking from the generator. The hydrogen leaked for several…
A nuclear Power Plant experienced a main generator hydrogen fire. Although a senior reactor operator (SRO) and auxiliary operators from another shift were available immediately, the need to provide…
This incident occurred during maintenance works after an outage at a turbine and generator unit of the plant. At the time of the incident, 15 maintenance technicians had already been working on the…
A technical failure in the High-Pressure turbine blades caused high vibrations in lubricating oil pipes. Some pipes broke off and the oil leak caught fire from hot surfaces. Also the generator's…

The incident occurred at the power generator of a nuclear power plant, in a non-nuclear area of the plant. Although hydrogen was use in the system, it was not affected by the fire. Oil leaked at a…

A catastrophic failure of the low pressure turbine followed by fire and flooding severely damaged the generator. The main turbine automatically tripped due to an erroneous mechanical over speed…
Leak from faulty hydrogen seal ignited by short circuit between inboard slip ring and outboard slip ring radial lead connection. Hydrogen flame caused damage to brush gear assembly and inboard slip…
A short circuit occurred in a bus bar system in a transformer building, causing a fire in adjacent switches. This was followed by the tripping out of the three refinery turbo-alternators, cutting off…
Gaseous hydrogen release in generator caused by turbine vibrations [Zalosh and Short, 1978]
The incident occurred in the turbine-generator hall of a nuclear power plant. Hydrogen leaked from the alternator and ignited. The hydrogen line was purged to stop the leak. The plant employees were…

A leak started on the hydrogen coolant cicrcuit of one of the power generators of the plant. It was indirectly detected because f the increased need to generate new hydrogen for cooling and it…