Fire in a transformer (616)
This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.
Fire in a transformer
A short circuit occurred in a bus bar system in a transformer building, causing a fire in adjacent switches. This was followed by the tripping out of the three refinery turbo-alternators, cutting off the National Grid supply, and loss of refinery electrical power, steam and air supplies for some 30 minutes. The cause of the incident was a fault in a 15 kV circuit breaker voltage transformer which led to a bus bar fault During the power loss and shutdown of plant, a hydrogen leak developed on a valve, and a tube of a fin-fan condense bank failed. Total damage attributed to the incident has been estimated at between 500,000 and 700,000 Frs. The fire fighters were busy for one and a half hours, they had to face ventilation problems and to ensure effective electrical isolation, before opening up electrical equipment casings.