HIAD Nature of the Consequences: Leak No Ignition


30 bottles with compressed hydrogen fell from a truck at a junction, because of speeding. The bottles started releasing hydrogen. Emergence team was called, and leak was stopped.
A leak occurred at a of a liquid withdrawal valve of a liquid hydrogen storage tank. The hydrogen escaped at the flange between the valve body and the upper part of the valve (flange with tongue and…

Compressed hydrogen escaped from reactor due to faulty gasket [Zalosh and Short, 1978]

Safety disc ruptured on LH2 tanker during offloading. The supply was refused due to possible contamination. [Ordin, NASA (1974)]

While disconnecting the liquid hydrogen filling line from the tanker, hydrogen escaped burning the man who was holding the hose; he was burned on hands and stomach. [Ordin, NASA (1974)]

During an LH2 transfer from a tanker, the burst disc ruptured at 50 psi (ca. 3. 5 bar). The operator had turned on the pressure valve and left it unattended, permitting pressure build-up past the…

While pressurizing a liquid hydrogen tanker for the transfer, a rupture disc burst. The tanker pressure was 22 psig (ca. 1. 5 bar). The relief valve was set at 27 to 29 psig (1. 9 to 2 bar). The…

During preparations for off-loading of a commercial tanker, the trailer experienced an overpressure causing the 50 psig (ca. 3. 5 bar) relief valve to open and also the rupture of the 70 psig (ca.…

A full liquid hydrogen tanker was parked off highway to permit drivers to eat and switch seats. While at site, high pressure caused safety devices to function. No fire or damage. [Ordin, NASA…

The operator detected a leak of aerosol hydrocarbons (diesel, hydrogen and hydrogen sulphide) in the diesel desulphurisation unit, causing a release of hydrogen and hydrogen sulphide at the top of…
The incident occurred in the hydrogenation reactor and products cooling unit. The reactor operated under vacuum conditions and the cooling medium was water. Toxic, flammable and explosive substances…

A liquid hydrogen trailer was delivering hydrogen at a customer site. The operation was occurring at the correct pressure, when one burst disc failed prematurely. No ignition occurred. The…

During a patrol, an operator detects a hydrogen leak in a refinery on a footbridge 30 meters high. The origin of the leak is identified 4 days later on a pipe under insulation. The operator proceeds…
In a fertilizer manufacturing plant, during his inspection round, an operator detected a hydrogen leak at a flange of an exchanger located between the conversion and decarbonisation stages of the…
A 40,000-litre capacity tanker carrying liquid hydrogen tipped over into a ditch on a curve in an intersection while travelling on a municipal road at the edge of town. The lorry had just left a…

A liquid hydrogen tanker had an accident on a highway. The tank was containing only with gaseous hydrogen. When going into curve, the tanker started to weave and pushed to side of road. It rolled…

The accident occurred on highway with a loaded LH2 tanker. the trailer started to jack­ knife after driver applied brakes, it swung around 180° and continued to slide into the shoulder. The…

A vehicle transporting 54 compressed hydrogen cylinders stopped at a railroad crossing and was struck from behind by a tractor trailer that did not slow down. Due to the impact, the cylinders were…

A tanker-tractor carrying liquid hydrogen overturned and lost vacuum insulation. The hydrogen boiled and vented, but there was no ignition. The potential for fire or explosion, however, led to…

This incident consisted in the accidental release of a CGH2 tube trailer after that it had rolled sideward on the ground. A hydrogen delivery company driver arrived at the customer site to…