Roll-over of a CGH2 tube trailer
This incident consisted in the accidental release of a CGH2 tube trailer after that it had rolled sideward on the ground. A hydrogen delivery company driver arrived at the customer site to investigate a reported leaking valve on a hydrogen trailer. The driver arrived with a full trailer in the event that the leaking valve could not be repaired on the spot. After confirming the leak, the driver decided to swap the trailers. The new trailer had just been lowered on its landing gear and separated from the tractor, when the ground gave away, causing the trailer to roll on its side. The stainless steel vent stacks on the top of the trailer were pushed up when they impacted the ground. As a result, six valves were immediately sheared off, and their contents began to vent. The entire contents of the six tubes vented within about 90 seconds. No flames were observed and no secondary damage indicated the presence of flames. The local emergency services and the hydrogen company experts decided to let all the 6 leaking tubes venting and proceeded to vent manually the other tubes still intact, till the whole load was released to the atmosphere.

The INITIATING CAUSE was the roll-over of the trailer because positioned on weak ground. An independent CONTRIBUING CAUSE preceding the initiating one, was the need to swap trailers due to the leaking of a valve on the previously installed trailer. The ROOT CAUSE could be combination of lack of proper location for the delivery of trailers at the customer location and/or the lack of a step requiring the driver to check the ground situation before installing the trailer.