During the transit of 10 000 gallons (ca. 39000 l) LH2 transport vessel, the venting rate became extremely high . The annular vacuum appeared to be lost showing large patches of condensed water at…
Excessive delay in trip resulted in over-pressure on the liquid hydrogen tank, requiring manual venting. This resulted in releasing of 2750 cu ft of hydrogen [Zalosh and Short, 1978]
The drivers failed to lower the internal pressure of a liquid hydrogen tanker before leaving plant. Therefore they had to stop en route and vent 4000 scf of hydrogen. [Zalosh and Short, 1978]
A liquid hydrogen tanker was returning empty to the base, when a pressure build-up forced the drivers to perform a manual venting. [Zalosh and Short, 1978]
The drivers failed to stabilise the tank pressure after having delivered the liquid hydrogen. Therefore they had to stop and perform a manual vent on journey back to the base. [Zalosh and Short,…
Before loading it with liquid hydrogen, the cyrogenic tank had been purged with nitrogen for maintenance work. After the loading, the drivers failed to stabilise the internal pressure of the tank,…
The pressure building valve opened due to vibration from the road, causing the build-up of the internal pressure. The drivers performed a hydrogen venting and re-sealed the valve. [Zalosh and…
A pressure build-up in the tank of a liquid hyrogen tanker caused the drivers to vent 6000 cu ft of hydrogen to reduce the pressure. [Zalosh and Short, 1978]
Pressure buildup in tank was manually vented by driver releasing 1000 cu ft [Zalosh and Short, 1978]
The tank of a liquid hydrogen tanker was manually vented prematurely on its empty return trip. 9,000 cu ft werereleased [Zalosh and Short, 1978]
While returning to the base, a liquid hydrogen tanker had to be vented twice. The cause of the overpressure was a malfunctioning scale which allowed a slight overload of hydrogen. [Zalosh and…
At an off-site LH2 fill station, a LH2 trailer hit the GH2 purge shut-off valve handle. The tubing attached to the purge valve was bent on both ends but did not leak. [Ordin, NASA (1974)]
During a welding operation on a LH2 fill line it was discovered that LH2 was still in the tank although it should have been drained. Hence the potential for a major explosion existed. [Ordin, NASA…
An LH2 trailer-tractor was returning to the base after a hydrogen delivery at a customer. The trailer was almost empty. Nevertheless, the drivers noticed an increase in the trailer internal…
An LH2 trailer-tractor was returning to the base after a hydrogen delivery at a customer. The trailer was almost empty. Nevertheless, the drivers noticed an increase in the trailer internal…
An LH2 trailer had just delivered hydrogen to a customer. The vehicle exited the plant, weighted the trailer parked to get the weight receipt. While in the building, a safety device activated due…
A LH2 trailer had delivered hydrogen to a customer and on the way was heading back to base, when the tank pressure rose from 40 psi to 128 psi. The drivers stopped at a truck parking place and…
A LH2 trailer was traveling to delivery hydrogen to a customer, while the drivers noticed an increase in trailer pressure. To avoid the possibility of having the safety vent open while on the road…
A LH2 trailer/truck had delivered liquid hydrogen to a customer site and was travelling back empty to the base. The drivers noticed an increase in trailer pressure. To avoid the possibility of…
A LH2 trailer had just delivered hydrogen to a customer and was travelling on a highway returning to the base, when the driver noticed that the pressure inside the tank was increasing rapidly. The…