Manual venting from a LH2 tanker in transit
Before loading it with liquid hydrogen, the cyrogenic tank had been purged with nitrogen for maintenance work. After the loading, the drivers failed to stabilise the internal pressure of the tank, which was still too warm. A release of 6000 cu ft of hydrogen was necessary to avoid over-pressure. [Zalosh and Short, 1978]
Event Date
December 23, 1974
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes

The INITIATING CAUSE was the risk of pressurisation which triggered a manual venting of hydrogen to reduce the internal pressure. The ROOT CAUSE was that the usual procedure for the loading of the tank had been performed, without considering that the tank had been completely emptied of cold hydrogen and was at room temperature. An adaptation of the usual procedure should applied in these cases.