Two False Hydrogen Alarms in Research Laboratory
Hydrogen alarms went off in a research laboratory and the fire department was called, but no hydrogen leak was detected. The hydrogen system was leak-checked with helium and found to be leak-free except for a very small leak in the manifold area. The manifold leak was fixed, but because of its small size, it was not thought to be the likely source for the hydrogen alarm trigger. While hydrogen was removed from the system for leak-testing, the hydrogen alarm went off again, and again the fire department responded. There was no hydrogen present in the system to trigger this alarm. Other sources within the building were checked to see what may have set off the alarm, but none were found. One research area uses small amounts of hydrogen, but laboratory logs indicate that none was being used at the time the alarm sounded. Carbon monoxide was also being investigated as a possible alarm trigger. The cause for the alarm has not yet been determined, but the investigation continues. There were no injuries or property damage associated with this event.
The research laboratory used hydrogen to create a very pure flame for a lathe to create fiber optic cables. The pure flame is important for the vapor deposition process used in the creation of the fiber optic cables. Hydrogen cylinders (ten 300-cubic foot cylinders for a total of 3,000 cubic feet or 85,950 liters) are located on the first floor, joined together by a manifold, and then piped for use on the 5th floor of the building. A hydrogen leak-detection system with alarms is located along the hydrogen path from the manifold to the point of use. The detectors used are combustible gas detectors that are calibrated for hydrogen.