Hydrogen Leak in Auxiliary Building
A power plant reported a hydrogen leak inside an auxiliary building. The given plant was in cold shutdown at the time of the event. The discovery of this problem was as a result of an unassociated event involving the activation of a chlorine monitor in the control building. When additional samples indicated no chlorine gas, the shift supervisor ordered further investigation into other plant areas. Because there was no installed detection equipment, portable survey instruments were used to determine gaseous mixtures. Hydrogen was detected in the auxiliary building at 20 to 30 percent of the lower flammability limit (LFL) for hydrogen. A level of about 30 percent of LFL corresponds to about 1.2 percent hydrogen by volume.
When hydrogen was discovered in the auxiliary building, the operator isolated the cryogenic hydrogen skid outside the turbine building and soon located the source of the leak as packing on a globe valve in a small line to the volume control tank (VCT). The operator opened doors that quickly caused the hydrogen to dissipate. The globe valve was of a conventional design and had no special packing. The globe valve was located in a vertical pipe chase where little ventilation was present because of ongoing HVAC testing. Besides being used as a cover gas in the VCT, hydrogen from the skid is used to cool the generator.