Near Accident in H2 Compressor Room
Incident Date
When Incident Was Discovered
Severity
Incident
Was Hydrogen Released?
Yes
Was There Ignition?
Yes
Damage and Injuries
Probable Cause
Characteristics
Describe the incident, including corrective steps taken and their result.
The malfunctioning of the non-return valve of the hydrogen compressor caused the pressure between the hydrogen bottle and the compressor to rise up to the maximum allowed pressure of 275 barg. As a consequence, as foreseen by the safety system, the rupture disk of the safety valve broke and the hydrogen content of the gas bottle and the pipe section involved was released on top of the building. The flame was seen for a very short period by a guard, and could have been caused by the following series of events:
- Expansion of hydrogen at the end of the exhaust pipe.
- Consequent mixing of hydrogen and air up to a near-stoichiometric mixture and increase of gas temperature.
- Mixture ignition due to sparks from static electricity generated by gas molecule friction against suspended dust particles. The safety system properly reacted to a malfunctioning component of the gas distribution system and avoided any risk to personnel or property.