Pressure Relief Device Fails at Fueling Station
A pressure relief device (PRD) valve failed on a high-pressure storage tube at a hydrogen fueling station, causing the release of approximately 300 kilograms of hydrogen gas. The gas ignited at the exit of the vent pipe and burned for 2-1/2 hours until technicians were permitted by the local fire department to enter the station and stop the flow of gas. During this incident the fire department evacuated nearby businesses and an elementary school, closed adjacent streets, and ordered a high school to shelter in place.
There were no injuries and very little property damage. The corrugated roof on an adjacent canopy over a fueling dispenser was slightly singed by the escaping hydrogen flame, causing less than $300 in damage.
The station's operating systems worked as they were designed to function in an emergency. All equipment and fuel supplies were completely isolated, and all storage vessels were well within acceptable and safe pressure and temperature limits prior to and throughout the incident.
After a thorough analysis of the incident was conducted, corrective actions were taken to replace PRD valves, heighten vent stacks, modify response procedures and improve communication protocols with first responders. A considerable amount of time was taken to review the station design, evaluate emergency action plans and procedures, meet with the public, train first responders, and conduct follow-up drills with employees and first responders. The station reopened nine months after the incident and has been fully operational since that time.