Failure of Stainless Steel Valves due to Hydrogen Embrittlement
Difficulties were experienced with two solenoid-operated globe valves in a charging system. When shut, the valves could not be reopened without securing all charging pumps. During a refueling outage, the two valves were disassembled and examined to determine the cause of the malfunction. It was found that disc guide assembly springs in both valves had undergone complete catastrophic failure. The springs, which initially had 25 coils, were found in sections of only 1-2 coils. Metallurgical analysis of the failed springs attributed the probable cause of failure was due to hydrogen embrittlement. The springs are made of 17-7 PH stainless steel.
Discussion with the valve manufacturer revealed that similar failures occurred on three previous occasions. These spring failures were also attributed to hydrogen embrittlement.