Laboratory Technician Fatally Burned When Leaking Hydrogen Ignites
A laboratory technician died and three others were injured when hydrogen gas being used in experiments leaked and ignited a flash fire.
The incident occurred in a 5,700-square-foot, single-story building of unprotected non-combustible construction. The building was not equipped with automatic gas detection or fire suppression systems.
Employees in the laboratory were conducting high-pressure, high-temperature experiments with animal and vegetable oils in a catalytic cracker under a gas blanket. They were using a liquefied petroleum gas burner to supply heat in the process.
Investigators believe that a large volume of hydrogen leaked into the room through a pump seal or a pipe union, spread throughout the laboratory, and ignited after coming into contact with the operating LPG burner some 10 to 15 feet away. The flash fire engulfed the people in the room.
Other employees used portable fire extinguishers to extinguish the localized fires caused by the flash fire. The fire department received notification at 2:36 pm. Because the fires were extinguished by the time they arrived, fire fighters provided emergency care to the injured. Damage was estimated as $25,000.