Leak on Compressor at Fueling Station
Incident Date
When Incident Was Discovered
Severity
Near-Miss
Was Hydrogen Released?
Yes
Was There Ignition?
No
Setting
Equipment
Damage and Injuries
Probable Cause
Describe the incident, including corrective steps taken and their result.
A vehicle fill depleted the high-pressure hydrogen inventory. The compressor turned on to refill the storage by compressing 60 psig gas from a liquid hydrogen tank up to the 5500 psig storage pressure. After running about 2 hours, a crankshaft bearing started to fail. This allowed greater movement of the shaft, which led to a shaft seal leaking hydrogen. The compressor shut down on low suction pressure and then the system was shut down using the e-stop by the emergency responders.