Liquid Hydrogen Tank Boiling Liquid Expanding Vapor Explosion (BLEVE) Incident
A rupture disc blew on a 9,000-gallon liquid hydrogen tank, causing the vent stack to exhaust cold gaseous hydrogen. Emergency responders were called to the scene. To stabilize the tank, about 50% of the hydrogen was removed from the tank except for a small volume in the heel of the tank that could not be removed manually. The tank vacuum was lost. Firemen sprayed the tank with water and directed a stream onto the fire exiting the vent stack. The water was channeled directly into the open vent stack, and the exiting residual hydrogen gas (as cold as -423˚F) caused the water in the vent stack to freeze. The water freezing caused the vent stack to be sealed off, disabling the only exit for the cold hydrogen gas. After a time, the residual hydrogen gas in the tank warmed up, causing the tank to over-pressurize and rupture with an explosion known as a BLEVE (boiling liquid expanding vapor explosion).