Saltwell Pump May Have Been Operated While the Standard Hydrogen Monitoring System was Not in Operational Mode
One morning a saltwell pump was placed in operation. Operation of this equipment requires that the Standard Hydrogen Monitoring System (SHMS) cabinet be in operation. Later that morning, during the morning surveillance rounds, the Standard Hydrogen Monitoring System (SHMS) cabinet was found not to be in the operational mode.
On the previous day, the night shift saltwell operator assigned to run the saltwell pump had placed the SHMS monitor in operational mode; however, the saltwell system was not started at this time. Shift turnover was conducted and the condition of the SHMS was turned over to the appropriate saltwell operator and shift manager. During the day shift the day shift operator assigned to the complex received approval from the operations engineer to place the SHMS in "dry out" non-operational mode. Shift turnover was conducted and the saltwell operators did not know the condition of the SHMS had changed. The routine operators turned over the change in status among themselves. The shift managers, however, did not effectively communicate the status of the SHMS during their turnover activity.
The direct cause was attributed to the failure to use and follow available procedures. The night shift saltwell operator assigned to run the saltwell pump had placed the SHMS monitor in operational mode in accordance with appropriate procedure documentation. The next evening, the same night shift saltwell operator was again assigned to saltwell pumping activities. This operator "listened to the unit", concluded that the unit was running, and made the assumption that the SHMS was in operational mode. The operator did not use an available procedure which required him to confirm through physical verification the operational status of the SHMS. The pump was then started, without the SHMS monitor configured in the proper operational mode.