Release of Stored Hydrogen as Water Temperature Increases
Incident Date
When Incident Was Discovered
Severity
Non-Event
Was Hydrogen Released?
No
Was There Ignition?
No
Equipment
Damage and Injuries
Probable Cause
Describe the incident, including corrective steps taken and their result.
During an external review of the facility safety basis document, it was identified that the accident analysis for the pool cell area hydrogen explosion did not account for release of stored hydrogen from the pool cell water as the temperature of the water increases. The analysis only accounted for the hydrogen generated by radiolysis. A loss of pool cell cooling occurring concurrently with a loss of ventilation would result in a higher concentration of hydrogen in the pool cell area than calculated in the safety basis. The safety basis document is being revised to account for the increase in hydrogen concentration.