Potential Catalyst Fire Hazard with Oxygen Generator Filter Change-out Maintenance
Within the International Space Station (ISS) oxygen generator, an increase in differential pressure across a pump supplying return water to a PEM electrolyzer fuel cell stack had persisted over a 4-month period and was approaching the shut-off limit for the system. This decrease in performance was suspected to be caused by water-borne catalyst fines containing platinum black and Teflon®* binder materials, shed by the fuel cell stack, and accumulated within the pump's inlet filter. Maintenance in the field was required.
The system had been designed for factory maintenance, and no contingency had been planned to handle field maintenance for such a circumstance. An initial assessment of hazards for the proposed filter maintenance raised the concern that opening the water line would release hydrogen gas from pressurized water, and with the sudden exposure of the debris collected on the filter to oxygen from outside, put both fluids in contact with the catalyst fines on the filter. Dry catalyst is known to heat to temperatures over 800 °C when exposed to hydrogen and oxygen. This could pose a fire hazard to personnel and surroundings. In addition, exposure of the Teflon binder to high temperatures can produce micron-scale Teflon particles, hydrogen fluoride (HF), and carbonyl fluoride (COF2) that pose an acute toxic inhalation hazard. However, water in the system will mitigate heat generation by a combination of heat sinking and physically limiting the availability of oxygen to approach the catalyst quickly. The factors that would prevail were not known. No action could be taken until these potential hazards were better understood.
* Teflon® is a registered trademark of E.I. DuPont de Nemours and Company, Wilmington, Delaware.