Leak in Liquid Hydrogen Pump Causes Explosion/Fire at Hydrogen Transfilling/Pumping System
A leaking liquid hydrogen cryogenic pump shaft during the process of filling a gaseous tube delivery trailer to 2400 psi at a liquid hydrogen transfilling location caused a series of explosions and a fire. After approximately 30 minutes of filling, the operator heard a single loud explosion and then saw flames and ripples from heat generation near the ground in the hydrogen fill area. The operator quickly actuated the emergency alarm system that shut down the cryogenic pump and closed the air-actuated valves on the cryogenic pump supply line. After this shutdown, three smaller explosions were heard as well as the sound of gas releasing from a safety relief valve. The fire department was called to the scene and participated in the final shutdown of the hydrogen system as the fire was extinguished prior to their arrival. The partially filled tube trailer (~ 1800 psi) was disconnected and moved away from the incident area to a safe location. There were no injuries from this incident and only a small amount of equipment damage with some floor charring.
A leak at the cold end packing of the liquid hydrogen pump was determined to be the source of the hydrogen that exploded and burned. The ignition source was most likely static electricity or frictional energy on the cryogenic pump shaft. A Notice of Violation was issued by the fire department that prevents the start-up of the liquid hydrogen system until all necessary safeguards are in place to re-start the system. A thorough investigation followed this incident and a summary is provided in Attachment 1. Highlights in Attachment 1 include findings of the cryogenic pump disassembly, operation of the shutdown pressure switch, speculation that the nitrogen purge system was inoperative, as well as more incident details.