Hydrogen Gas Present in Forklift Battery Charging Facility

Hydrogen Gas Present in Forklift Battery Charging Facility

Incident Date
When Incident Was Discovered
Severity
Incident
Was Hydrogen Released?
Yes
Was There Ignition?
No
Equipment
Damage and Injuries
Probable Cause
Contributing Factors
Describe the incident, including corrective steps taken and their result.

A routine security patrol reported a strong odor of sulfur coming from a battery charging facility. The battery charging facility is used for charging the various forklift batteries for the shipping and receiving operation. The building is approximately 450 sq. ft. and has four charging stations. Emergency response was initiated and the incident commander responded to the scene. Initial air monitoring indicated readings above the Lower Explosive Limit (LEL) for hydrogen gas. The local fire department responded and setup for the situation. Facilities personnel responded and turned power off to the building. The building was ventilated and verified to be safe by the fire department. There were no injuries or damage.

The exhaust fan for the building failed, allowing hydrogen gas to build up. A mechanical failure in the fan caused the automatic on/off sensor to overheat and shut the fan off.

The Preliminary Hazard Assessment (PHA) did not include the hazard of hydrogen buildup in the building from an exhaust fan failure. Because of this, there was no back-up exhaust system in place to keep this from becoming a problem.

The original PHA for the battery charging facility did not address the hazard of hydrogen buildup from an exhaust fan failure. The PHA will be revised to include this new information. Some additional concerns that were addressed were the addition of a vent and cooling system, a hard-wired breaker box switch, and the posting of the forklift battery charging procedures in the building. These additional concerns did not contribute to the occurrence, but were identified as improvements.

Lessons Learned

The simplicity of this situation has made us aware that increased consideration must be given to all aspects of the workplace when preparing preliminary hazard assessments. Some hazardous situations appear so trivial that they can be easily overlooked and serious consequences not understood. Also, some hazardous situations are not readily recognized by the layman and we should consider inviting professionals from other organizations to assist us with assessments and reviews on a periodic basis.

Adequate ventilation of battery charging facilities is addressed in the Lessons Learned Corner on this website.

Key:

  • = No Ignition
  • = Explosion
  • = Fire
Hydrogen Incident Summaries by Equipment and Primary Cause/Issue
Equipment / CauseEquipment Design or SelectionComponent FailureOperational ErrorInstallation or MaintenanceInadequate Gas or Flame DetectionEmergency Shutdown ResponseOther or Unknown
Hydrogen Gas Metal Cylinder or Regulator 3/31/2012
4/30/1995
2/6/2013
4/26/201012/31/1969  3/17/1999
11/1/2001
12/23/2003
Piping/Valves4/4/2002
2/2/2008
5/11/1999
4/20/1987
11/4/1997
12/31/1969
8/19/1986
7/27/1991
12/19/2004
2/6/2008
10/3/2008
4/5/2006
5/1/2007
9/19/2007
10/31/1980
2/7/20091/24/1999
2/24/2006
6/8/1998
12/31/1969
2/7/2009
9/1/1992
10/31/1980
10/3/2008 
Tubing/Fittings/Hose 9/23/1999
8/2/2004
8/6/2008
9/19/2007
1/1/19829/30/2004
10/7/2005
 10/7/2005 
Compressor 10/5/2009
6/10/2007
8/21/2008
1/15/2019
  10/5/20098/21/2008 
Liquid Hydrogen Tank or Delivery Truck4/27/198912/19/2004
1/19/2009
8/6/200412/31/1969 1/1/197412/17/2004
Pressure Relief Device7/25/2013
5/4/2012
1/15/2002
1/08/2007
12/31/1969    
Instrument1/15/20193/17/1999
12/31/1969
2/6/2013
  11/13/73  
Hydrogen Generation Equipment7/27/1999  10/23/2001   
Vehicle or Lift Truck 7/21/2011    2/8/2011
12/9/2010
Fuel Dispenser 8/2/2004
5/1/2007
6/11/2007
9/19/2007
 2/24/2006
1/22/2009
   
Fuel Cell Stack      5/3/2004
12/9/2010
2/8/2011
Hydrogen Cooled Generator   12/31/1969
2/7/2009
   
Other (floor drain, lab
anaerobic chamber,
heated glassware,
test chamber,
gaseous hydrogen
composite cylinder,
delivery truck)
 11/14/1994
7/21/2011
7/27/1999
6/28/2010
8/21/2008
12/31/1969
3/22/2018
  6/10/2019
  • = No Ignition
  • = Explosion
  • = Fire