Hydrogen Furnace Leak
The hydrogen feed system for the furnaces inside a pit furnace developed a leak. The leak was on the hydrogen dryer inside a shack attached to a building. The leak vented 200 psig hydrogen into the shack. The hydrogen low-pressure alarm sounded. No furnace operators were present at the time. An estimated 10,000 standard cubic feet of hydrogen vented. T
he hydrogen release was caused by a failure of an elastomeric pressure seal on the body of a particulate filter located in the hydrogen supply circuit of the Pit Furnace. After a similar event a month earlier, the cause was identified as a simple seal failure; however an independent engineering review after the present incident showed the cause to be system overpressure, caused by regulator failure.