Hydrogen Fire due to the Installation of an Incorrectly Sized Gasket at a Solvent Manufacturing Plant
Overview
A hydrogen leak and fire occurred due to the installation of an incorrectly sized gasket at a solvent manufacturing plant. A worn gasket was accidentally replaced with a new gasket that was smaller than the standard one, and the system could not withstand the operational pressure of the hydrogen, causing the hydrogen to leak and ignite a small fire. Furthermore, a nearby gasket was damaged by the fire, causing a larger quantity of hydrogen to leak, and the fire spread. As nitrogen was substituted for the combustible hydrogen gas in the piping at an early stage of the fire, damage was limited to the immediate area. If the hydrogen had not been quickly purged from the system, the fire damage would have been greater. It is assumed that gasket management at a turnaround shutdown was the cause.
Incident Synopsis
A worn gasket was replaced with a somewhat smaller one, and was used to rejoin the flange of a valve at a solvent manufacturing plant. The system was then activated and the system pressure gradually rose, until the plant shifted into usual continuous operation. After operation restarted, the smaller gasket, which was about 1/7th the width of the standard one, could not withstand the pressure of the compressed hydrogen. Hydrogen began to leak from the flange and was ignited by static electricity, causing a small fire in the thermal insulation. A flange of an adjacent drain valve, and the thermal insulation on the valve, were also damaged. A large quantity of hydrogen leaked from the flange of the drain valve, and the fire spread. The plant was urgently shut down and employees carried out initial fire fighting and nitrogen substitution. The fire department was notified about the fire, and the fire fighters injected nitrogen into the system until the fire burned itself out and was confirmed to be extinguished.
The cause of the incident was human error in removing a worn component and installing the wrong replacement part. After a gasket replacement, a leak test is usually performed. The new gasket passed the leak test at the time of this incident, probably because the test duration was very short.
The physical damage incurred during the incident was concentrated on nearby piping and surrounding thermal insulation.