Hydrogen Explosion in a Styrene Plant
A hydrogen explosion and fire occurred in the benzene unit of a styrene plant in a large petrochemical complex. The unit was being restarted following a scheduled maintenance shutdown. The explosion followed the release of about 30 kilograms of 700-psig hydrogen gas from a burst flange into a compressor shed. Two men were killed and two others were injured. If it had not been a holiday, the death toll and injuries would probably have been much worse.
The operators were bringing the plant online and increasing the hydrogen circulation pressure. About 10-15 seconds before the explosion, they heard a pop and then a loud hiss of pressure being released within the compressor shed. Witnesses reported seeing a white flash and then a large fireball. The fires burned out in 2-3 minutes, except for benzene leaking from a ruptured flange that continued to burn for 8 hours because there was no emergency shutoff valve to isolate the vessel.
The metal roof and heavy metal door of the compressor shed were blown several hundred feet away. Piping, ladders, and other steel equipment were severely deformed by the blast. Ceilings fell and instruments were damaged in the control house, about 75 feet away from the compressor shed. Office buildings about 1200 feet away sustained damages to windows, doors, and masonry.