Hydrogen Explosion and Iron Dust Flash Fires in Powdered Metals Plant
Operators in a powdered metals production facility heard a hissing noise near one of the plant furnaces and determined that it was a gas leak in the trench below the furnaces. The trench carried hydrogen, nitrogen, and cooling water runoff pipes as well as a vent pipe for the furnaces.
Maintenance personnel presumed that the leak was nonflammable nitrogen because there had recently been a nitrogen piping leak elsewhere in the plant. Using the plant's overhead crane, they removed some of the heavy trench covers. They determined that the leak was in an area that the crane could not reach, so they brought in a forklift with a chain to remove the trench covers in that area.
Eyewitnesses stated that as the first trench cover was wrenched from its position by the forklift, friction created sparks followed immediately by a powerful explosion. Several days after the explosion, Chemical Safety Board (CSB) investigators observed a large hole (~3x7 inches) in a corroded section of hydrogen vent piping inside the trench.
As the hydrogen-air mixture in the partially open trench exploded, the resulting overpressure dispersed large quantities of iron dust from the rafters and other surfaces in the plant, and some of this dust subsequently ignited. Eyewitnesses reported that embers were raining down and igniting iron dust flash fires in the area. Visibility was so poor due to dust and smoke that even with a flashlight, it was impossible to see more than 3 or 4 feet. Three plant employees eventually died from burn injuries despite wearing supposedly flash-fire-resistant garments. Two others suffered smoke-inhalation injuries. Due to the extensive nature of the injuries, and the abundance of both hydrogen and combustible dust present at the time of the incident, it is difficult to specifically determine which fuel, if not both, caused the fatal injuries to the victims.